Electrical Reference Card
One page. Voltage drop lengths, breaker and wire pairing, motor FLC.
$3.99
BuyNEC Table 310.16 — temperature correction, bundling, terminal limits, NM-B rule, continuous loads
Check what a given conductor is good for after derating, or find the smallest wire that meets your load. Uses the same Table 310.16 bases and factors as the live calculator.
| Size | 60°C / TW / NM-B final | 75°C / THWN / THW | 90°C / THHN start |
|---|---|---|---|
| 14 AWG | 15A | 20A | 25A |
| 12 AWG | 20A | 25A | 30A |
| 10 AWG | 30A | 35A | 40A |
| 8 AWG | 40A | 50A | 55A |
| 6 AWG | 55A | 65A | 75A |
| 4 AWG | 70A | 85A | 95A |
| 3 AWG | 85A | 100A | 115A |
| 2 AWG | 95A | 115A | 130A |
| 1 AWG | 110A | 130A | 145A |
| 1/0 | 125A | 150A | 170A |
| 2/0 | 145A | 175A | 195A |
| 3/0 | 165A | 200A | 225A |
| 4/0 | 195A | 230A | 260A |
| 250 kcmil | 215A | 255A | 290A |
| 300 kcmil | 240A | 285A | 320A |
| 350 kcmil | 260A | 310A | 350A |
| 400 kcmil | 280A | 335A | 380A |
| 500 kcmil | 320A | 380A | 430A |
| Size | 60°C / TW | 75°C / THWN | 90°C / THHN start |
|---|---|---|---|
| 12 AWG* | 15A | 20A | 25A |
| 10 AWG | 25A | 30A | 35A |
| 8 AWG | 35A | 40A | 45A |
| 6 AWG | 40A | 50A | 55A |
| 4 AWG | 55A | 65A | 75A |
| 3 AWG | 65A | 75A | 85A |
| 2 AWG | 75A | 90A | 100A |
| 1 AWG | 85A | 100A | 115A |
| 1/0 | 100A | 120A | 135A |
| 2/0 | 115A | 135A | 150A |
| 3/0 | 130A | 155A | 175A |
| 4/0 | 150A | 180A | 205A |
| 250 kcmil | 170A | 205A | 230A |
| 300 kcmil | 195A | 230A | 260A |
| 350 kcmil | 210A | 250A | 280A |
| 400 kcmil | 225A | 270A | 305A |
| 500 kcmil | 260A | 310A | 350A |
*Minimum aluminum branch circuit = 12 AWG per NEC 310.106(B).
Per NEC Table 310.16, 310.15(B)(1), 310.15(C)(1), 110.14(C), 210.19(A), and 334.80. Verify with the current NEC and local amendments.

One page. Voltage drop lengths, breaker and wire pairing, motor FLC.
$3.99
Buy
15 pages. Ampacity, corrections, voltage drop, motor circuits, conduit fill.
$12.99
Buy
Quote electrical work and flag panel headroom before you price it.
Excel or Google Sheets. Best on a computer.
$29.00
Buy
Card, 15-page guide and the estimator workbook. All six files.
Excel or Google Sheets. Best on a computer.
$34.99
$45.98 if bought separately — save $10.99
BuyCheckout opens in a new tab.
After you size conductors, verify loads in the field and strip terminations cleanly.
As an Amazon Associate, TestTalkHQ earns from qualifying purchases. Prices and availability subject to change.
NM-B / Romex: NEC 334.80 limits final ampacity to the 60°C column even though individual conductors may be 90°C rated. The tool still starts derating from the correct base column per insulation selection, then caps at 60°C for NM-B.
Terminals: NEC 110.14(C) caps the usable ampacity at the terminal temperature column unless equipment is listed and marked for a higher temperature.
Both factors: Ambient correction (Table 310.15(B)(1) style factors embedded as live) and bundling (Table 310.15(C)(1) style) multiply together before the terminal/NM-B cap.
Continuous loads: NEC 210.19(A) — when continuous is selected, required ampacity is 125% of load for sizing in find mode; in check mode the “max continuous load” line divides final ampacity by 1.25.