12V Wire Gauge Ampacity Chart by Length

Maximum continuous amps at 3% drop on 12 V copper, one-way feet — a grid, not a single-scenario calculator

Same round-trip math as the 12V DC wire gauge calculator (V_drop = I × R × 2 × L / 1000, NEC Ch. 9 Table 8 copper at 75°C). This page is for common lengths. Oddball 17 ft runs belong in the calculator. Method: sizing guide.

How to read the table

Rows are AWG (4 through 14). Columns are one-way length. Each cell is the largest continuous current that stays at or under 3% of 12 V (0.36 V) for that gauge and length. Find your one-way feet on the top, read down until the amp number exceeds your load, then use that row or thicker. Thicker is smaller AWG number.

Example: 20 A at 10 ft one-way. 10 AWG cell is 14.5 A — too small. 8 AWG is 23 A — that row works. 20 A at 20 ft: 8 AWG is only 11.6 A; 6 AWG is 18.3 A — still short; 4 AWG is 29 A — use 4 AWG or run the calculator if you can live with 5% drop.

AWG (copper)5 ft10 ft20 ft30 ft50 ft
4 AWG117 A58 A29 A19.5 A11.7 A
6 AWG73 A37 A18.3 A12.2 A7.3 A
8 AWG46 A23 A11.6 A7.7 A4.6 A
10 AWG29 A14.5 A7.3 A4.8 A2.9 A
12 AWG18.2 A9.1 A4.5 A3.0 A1.8 A
14 AWG11.5 A5.7 A2.9 A1.9 A1.1 A

Max continuous amps at 3% drop, 12 V, copper, round-trip = 2 × one-way. I_max = 0.36 × 1000 / (R × 2 × L). Not a chassis ampacity or fuse chart. 24 V at 3% roughly doubles these amp numbers (allowable volts double).

When a chart is the right tool

You already know the path is about 10 ft or 20 ft, the load is a catalog number (5 A pods, 15 A fridge), and you want a yes/no without opening a form. Shops tape this grid in the van. It is also the way to see, at a glance, that 14 AWG is a courtesy-light wire, not a light-bar wire, once the bumper is 10 ft of loom from the battery.

The chart is the wrong tool when length is 7 ft or 22 ft, when you need 4% or 2%, when the bank is 24 V, or when current is 47 A. Those four knobs are why the calculator exists. Welding-cable and 120 V extension-cord charts are different metals and voltages — do not cross-read extension cord gauge or welder gauge into a 12 V fridge circuit.

Chart vs calculator vs ampacity

Voltage-drop amps in a cell can exceed what you should fuse on that gauge in a hot engine bay. 4 AWG showing 117 A at 5 ft is a drop number, not permission to fuse 117 A on cheap insulation. After you pick a row, still fuse for the conductor and the accessory, and pick fuse vs breaker on purpose (comparison). If lights are already dim, skip the grid and measure — problems and solutions.

NEC 120/240 V drop uses the same R table but answers a different question (conductor size on a branch circuit). Use that calculator for premises wire. This grid is 12 V accessory copper only, 3% only, lengths listed only.

Interpolate only if you must. 15 ft is not the average of 10 and 20 — drop scales with L, so I_max scales with 1/L. Midpoints: take the longer column or type 15 into the calculator.

Related 12V Wiring Tools

Electrical

Electrical Reference Card

Electrical Reference Card

One page. Voltage drop lengths, breaker and wire pairing, motor FLC.

$3.99

Buy
Complete Electrical Reference Guide

Complete Electrical Reference Guide

15 pages. Ampacity, corrections, voltage drop, motor circuits, conduit fill.

$12.99

Buy
Electrical Job Estimator

Electrical Job Estimator

Quote electrical work and flag panel headroom before you price it.

Excel or Google Sheets. Best on a computer.

$29.00

Buy
BEST VALUE
Electrical Complete Bundle

Electrical Complete Bundle

Card, 15-page guide and the estimator workbook. All six files.

Excel or Google Sheets. Best on a computer.

$34.99

$45.98 if bought separately — save $10.99

Buy

See all Electrical products

Checkout opens in a new tab.