BuyNEC 215.2 / Article 220 — minimum ampacity, 125% continuous, conductor lookup
Build a load schedule, mark continuous loads, and compare calculated amps to standard breakers and 75°C conductor tables used in the tool.
Calculate feeder and service entrance conductor sizing per NEC 215.2 and Article 220. Enter your connected loads, apply demand factors, and get the minimum feeder ampacity, conductor size, and required overcurrent protection — with full step-by-step math so you can show your work at inspection.
Related tools: Circuit Breaker Sizing · Wire Ampacity Calculator · Residential load calculator (NEC 220.82)
| Portion of Load | Demand Factor | Application |
|---|---|---|
| First 3,000 VA | 100% | All occupancies |
| Next 3,001 to 120,000 VA | 35% | Dwelling units |
| Remainder over 120,000 VA | 25% | Dwelling units |
| Rule | NEC Section | Requirement |
|---|---|---|
| Minimum ampacity | 215.2(A)(1) | Not less than non-continuous load + 125% of continuous load |
| Minimum overcurrent protection | 215.2(A)(1) | Not less than non-continuous + 125% continuous |
| Demand factors permitted | 220.42, 220.53, 220.54 | Apply per applicable NEC section |
| Minimum feeder — dwelling | 215.2(A)(1) Ex. | 100A for a single dwelling |
| Load (Amps) | Aluminum Conductor | Copper Equivalent | Typical Application |
|---|---|---|---|
| 60A | 4 AWG Al | 6 AWG Cu | Sub-panel, small loads |
| 100A | 1/0 AWG Al | 4 AWG Cu | Small home service |
| 125A | 2/0 AWG Al | 2 AWG Cu | Average home service |
| 150A | 3/0 AWG Al | 1 AWG Cu | Medium home service |
| 200A | 4/0 AWG Al | 2/0 AWG Cu | Standard 200A service |

One page. Voltage drop lengths, breaker and wire pairing, motor FLC.
$3.99
Buy
15 pages. Ampacity, corrections, voltage drop, motor circuits, conduit fill.
$12.99
Buy
Quote electrical work and flag panel headroom before you price it.
Excel or Google Sheets. Best on a computer.
$29.00
Buy
Card, 15-page guide and the estimator workbook. All six files.
Excel or Google Sheets. Best on a computer.
$34.99
$45.98 if bought separately — save $10.99
BuyCheckout opens in a new tab.
Clamp meters, distribution gear, and conductors electricians use when sizing feeders.
As an Amazon Associate, TestTalkHQ earns from qualifying purchases. Prices and availability subject to change.
NEC 215.2(A)(1) sets the minimum ampacity for feeder conductors: they must carry the non-continuous load at 100%, plus the continuous load at 125%. A feeder serving 60A of continuous load and 40A of non-continuous load needs a minimum ampacity of (60 × 1.25) + 40 = 115A — not simply 100A. That is the value you compare to conductor ampacity tables.
The overcurrent device protecting the feeder follows the same sizing basis. The OCPD must be rated at not less than the non-continuous load plus 125% of continuous load, then you select the next standard device per NEC 240.6(A).
NEC Article 220 allows demand factors on specific load types because not everything runs at full load simultaneously. Common references include:
Residential (NEC 220.82 optional method): For dwelling units, the optional method in NEC 220.82 groups general lighting (3 VA per sq ft), small-appliance and laundry circuits, and fixed loads, then applies set demand factors. Use our residential load calculator (NEC 220.82) for that path.
Commercial (standard method): Commercial feeders typically follow the standard method — sum loads, apply Article 220 demand factors where permitted, and separate continuous vs. non-continuous classification for the 125% rule.