Feeder & service load

NEC 215.2 / Article 220 — minimum ampacity, 125% continuous, conductor lookup

Build a load schedule, mark continuous loads, and compare calculated amps to standard breakers and 75°C conductor tables used in the tool.

Calculate feeder and service entrance conductor sizing per NEC 215.2 and Article 220. Enter your connected loads, apply demand factors, and get the minimum feeder ampacity, conductor size, and required overcurrent protection — with full step-by-step math so you can show your work at inspection.

Related tools: Circuit Breaker Sizing · Wire Ampacity Calculator · Residential load calculator (NEC 220.82)

Embed this calculator Free · no API key · keep the attribution link

Copy the snippet below to embed this calculator on your site. The attribution link must stay intact and dofollow (no rel="nofollow"). Browse all embeddable calculators

<div class="ttq-embed" style="max-width:100%;margin:0 auto;">
  <iframe src="https://testtalkhq.com/embed/feeder-service-load-calculator/?theme=light&utm_source=embed" width="100%" height="980" frameborder="0" loading="lazy" scrolling="no" title="Feeder / Service Load Calculator — TestTalkHQ" style="border:0;max-width:100%;width:100%;"></iframe>
  <p style="font:400 13px/1.4 system-ui,sans-serif;text-align:center;margin:6px 0 0;">Powered by the <a href="https://testtalkhq.com/feeder-service-load-calculator/?utm_source=embed&utm_medium=referral&utm_campaign=calculator_embed&utm_content=feeder-service-load-calculator" target="_blank" rel="noopener">Online Feeder / Service Load</a> from <a href="https://testtalkhq.com/?utm_source=embed&utm_medium=referral&utm_campaign=calculator_embed&utm_content=feeder-service-load-calculator" target="_blank" rel="noopener">TestTalkHQ</a></p>
</div>

NEC Table 220.42 — General Lighting Demand Factors

Portion of LoadDemand FactorApplication
First 3,000 VA100%All occupancies
Next 3,001 to 120,000 VA35%Dwelling units
Remainder over 120,000 VA25%Dwelling units

NEC 215.2 — Feeder Sizing Rules Summary

RuleNEC SectionRequirement
Minimum ampacity215.2(A)(1)Not less than non-continuous load + 125% of continuous load
Minimum overcurrent protection215.2(A)(1)Not less than non-continuous + 125% continuous
Demand factors permitted220.42, 220.53, 220.54Apply per applicable NEC section
Minimum feeder — dwelling215.2(A)(1) Ex.100A for a single dwelling

Aluminum Service Conductor Sizes — Common Sizing

Load (Amps)Aluminum ConductorCopper EquivalentTypical Application
60A4 AWG Al6 AWG CuSub-panel, small loads
100A1/0 AWG Al4 AWG CuSmall home service
125A2/0 AWG Al2 AWG CuAverage home service
150A3/0 AWG Al1 AWG CuMedium home service
200A4/0 AWG Al2/0 AWG CuStandard 200A service

Electrical

Electrical Reference Card

Electrical Reference Card

One page. Voltage drop lengths, breaker and wire pairing, motor FLC.

$3.99

Buy
Complete Electrical Reference Guide

Complete Electrical Reference Guide

15 pages. Ampacity, corrections, voltage drop, motor circuits, conduit fill.

$12.99

Buy
Electrical Job Estimator

Electrical Job Estimator

Quote electrical work and flag panel headroom before you price it.

Excel or Google Sheets. Best on a computer.

$29.00

Buy
BEST VALUE
Electrical Complete Bundle

Electrical Complete Bundle

Card, 15-page guide and the estimator workbook. All six files.

Excel or Google Sheets. Best on a computer.

$34.99

$45.98 if bought separately — save $10.99

Buy

See all Electrical products

Checkout opens in a new tab.

Tools for feeder & service work

Clamp meters, distribution gear, and conductors electricians use when sizing feeders.

Panel
Square D QO140L200PG 200A load center

Square D QO140L200PG 200A Load Center

  • 40-space layout for subfeeders and branch breakers
  • QO series common in service upgrades
  • Matches 200A feeder and service planning
View on Amazon →
Meter
Fluke 117 electricians multimeter

Fluke 117 Electricians True RMS Multimeter

  • Dead-front checks before energizing panels
  • Non-contact voltage detection
  • CAT III 600V for distribution work
View on Amazon →
Find breakers
Klein ET310 circuit breaker finder

Klein Tools ET310 Circuit Breaker Finder

  • Map existing circuits before feeder changes
  • Built-in GFCI tester
  • Saves time during panel surveys
View on Amazon →
Insulated
Klein insulated screwdriver set

Klein 1000V Insulated Screwdriver Set

  • IEC 60900 insulation for energized-adjacent work
  • Useful for lugs, breakers, and panel terminations
  • Multiple profiles in one service kit
View on Amazon →

As an Amazon Associate, TestTalkHQ earns from qualifying purchases. Prices and availability subject to change.

NEC 215.2 — Feeder conductor sizing rules

NEC 215.2(A)(1) sets the minimum ampacity for feeder conductors: they must carry the non-continuous load at 100%, plus the continuous load at 125%. A feeder serving 60A of continuous load and 40A of non-continuous load needs a minimum ampacity of (60 × 1.25) + 40 = 115A — not simply 100A. That is the value you compare to conductor ampacity tables.

The overcurrent device protecting the feeder follows the same sizing basis. The OCPD must be rated at not less than the non-continuous load plus 125% of continuous load, then you select the next standard device per NEC 240.6(A).

Demand factors — when and how to apply them

NEC Article 220 allows demand factors on specific load types because not everything runs at full load simultaneously. Common references include:

  • NEC Table 220.42 — general lighting: First 3,000 VA at 100%, next 3,001–120,000 VA at 35%, remainder at 25% (dwelling units).
  • NEC 220.53 — fixed appliances: With four or more fixed appliances (excluding dryer, range, A/C, and heat), 75% may apply to the total.
  • NEC 220.54 — electric dryers: 5,000W or nameplate, whichever is larger, with additional rules for multiple dryers.
  • NEC 220.55 — cooking equipment: Demand tables for ranges and cooktops by quantity and rating.

Residential vs. commercial feeder calculations

Residential (NEC 220.82 optional method): For dwelling units, the optional method in NEC 220.82 groups general lighting (3 VA per sq ft), small-appliance and laundry circuits, and fixed loads, then applies set demand factors. Use our residential load calculator (NEC 220.82) for that path.

Commercial (standard method): Commercial feeders typically follow the standard method — sum loads, apply Article 220 demand factors where permitted, and separate continuous vs. non-continuous classification for the 125% rule.

Pro tip Aluminum is common for large feeders and services. Size from the aluminum column of NEC Table 310.16 (or engineering supervision where required), use connectors listed for aluminum, and follow manufacturer torque and antioxidant requirements.

Frequently asked questions

What is the minimum feeder size for a residential service?
For a single dwelling unit, the feeder must be sized for the calculated load but not less than 100A per NEC 230.79(C). Many new homes are built with 200A service to allow for EV and electrification.
What is the difference between a feeder and a branch circuit?
A feeder runs between service equipment (or another supply point) and the final branch-circuit overcurrent device. A branch circuit is downstream of the last OCPD before the load. Feeders fall under NEC Article 215; branch circuits under Article 210.
Do I need to apply the 125% rule to feeder conductors?
Yes. NEC 215.2(A)(1) requires feeder conductor ampacity not less than the non-continuous load plus 125% of the continuous load for loads operated as continuous (typically 3 hours or more).
Can I use aluminum conductors for feeders?
Yes, when permitted by the design. Size per NEC Table 310.16, use listed lugs and connectors, and follow termination preparation practices for aluminum conductors.