EV charger circuit sizing

NEC 220.57 continuous load, demand factors, breaker, and conductor sizing

Plan minimum circuit ampacity (125% rule), standard breaker size, copper or aluminum wire at 75°C with ambient correction, and a simple voltage-drop check. Use with our breaker sizing, wire ampacity, and voltage drop tools.

Embed this calculator Free · no API key · keep the attribution link

Copy the snippet below to embed this calculator on your site. The attribution link must stay intact and dofollow (no rel="nofollow"). Browse all embeddable calculators

<div class="ttq-embed" style="max-width:100%;margin:0 auto;">
  <iframe src="https://testtalkhq.com/embed/ev-charger-circuit-sizing-calculator/?theme=light&utm_source=embed" width="100%" height="980" frameborder="0" loading="lazy" scrolling="no" title="EV Charger Circuit Sizing Calculator — TestTalkHQ" style="border:0;max-width:100%;width:100%;"></iframe>
  <p style="font:400 13px/1.4 system-ui,sans-serif;text-align:center;margin:6px 0 0;">Powered by the <a href="https://testtalkhq.com/ev-charger-circuit-sizing-calculator/?utm_source=embed&utm_medium=referral&utm_campaign=calculator_embed&utm_content=ev-charger-circuit-sizing-calculator" target="_blank" rel="noopener">EV Charger Circuit Sizing</a> from <a href="https://testtalkhq.com/?utm_source=embed&utm_medium=referral&utm_campaign=calculator_embed&utm_content=ev-charger-circuit-sizing-calculator" target="_blank" rel="noopener">TestTalkHQ</a></p>
</div>
NEC 220.57 — EV charger demand factor reference
Number of chargersDemand factorNotes
1100%Full rated current — continuous load rule applies
2100%Both at full — no demand factor reduction
3100% of 2 largest + 75% of remainderNEC 220.57(B)
4+100% of 2 largest + 75% of remainderMulti-unit / fleet savings
Level 2 EVSE — common sizes (reference)
EVSE outputMin ampacity (125%)BreakerCopper wireAl wire
16A20A20A12 AWG10 AWG
24A30A30A10 AWG8 AWG
32A40A40A8 AWG6 AWG
40A50A50A6 AWG4 AWG
48A60A60A4 AWG3 AWG

Electrical

Electrical Reference Card

Electrical Reference Card

One page. Voltage drop lengths, breaker and wire pairing, motor FLC.

$3.99

Buy
Complete Electrical Reference Guide

Complete Electrical Reference Guide

15 pages. Ampacity, corrections, voltage drop, motor circuits, conduit fill.

$12.99

Buy
Electrical Job Estimator

Electrical Job Estimator

Quote electrical work and flag panel headroom before you price it.

Excel or Google Sheets. Best on a computer.

$29.00

Buy
BEST VALUE
Electrical Complete Bundle

Electrical Complete Bundle

Card, 15-page guide and the estimator workbook. All six files.

Excel or Google Sheets. Best on a computer.

$34.99

$45.98 if bought separately — save $10.99

Buy

See all Electrical products

Checkout opens in a new tab.

EVSE install and panel tools

Meters, conductors, and distribution gear electricians use on charger circuits.

Clamp
Klein Tools CL800 clamp meter

Klein Tools CL800 Digital AC/DC Clamp Meter

  • Confirm EVSE draw after install
  • True RMS for accurate loads
  • High-amp branch troubleshooting
View on Amazon →
Copper
Southwire 10 AWG stranded THHN

Southwire 10 AWG Stranded THHN (500 ft)

  • Typical 30 A branch / EV feeder building block
  • THHN/THWN-2 for conduit runs
  • Stranded for pulls
View on Amazon →
Panel
Square D QO 200A load center

Square D QO140L200PG 200A Load Center

  • Space for two-pole EVSE breakers
  • 200A main — service upgrade planning
  • QO series common in retrofits
View on Amazon →
Drivers
Klein 1000V insulated screwdriver set

Klein 1000V Insulated Screwdriver Set

  • IEC 60900 rated insulation
  • Breaker and EVSE terminations
  • Multiple profiles in one kit
View on Amazon →

As an Amazon Associate, TestTalkHQ earns from qualifying purchases. Prices and availability subject to change.

NEC 220.57 and continuous loads

EVSE is treated as a continuous load: branch circuit ampacity is not less than 125% of the equipment rating. This calculator follows the live tool: demand-adjusted total amps × 1.25, then next standard breaker from the embedded ladder, then smallest conductor in the embedded 75°C table that meets ampacity after ambient derating.

Multiple chargers: For 3 or 4 identical units, the live script applies 100% of two largest plus 75% of the rest (simplified equal-nameplate model).

Voltage drop The drop estimate uses the script’s mΩ/ft tables and two-wire length × current. It is a planning aid — use the full voltage drop calculator for precise runs.

NEC 625.40 dedicated branch circuit

The advisory block flags when “shared circuit” is selected — NEC 625.40 expects a dedicated branch circuit for EVSE. Always confirm with the AHJ.

Frequently asked questions

What breaker for a 32 A Level 2 charger?
32 A × 125% = 40 A minimum circuit ampacity; the script picks the next standard breaker ≥ that value (40 A) and matches conductor to derated table ampacity.
Can I share the EV circuit with receptacles?
No — select “dedicated” for a compliant layout; the tool warns if you select shared.
Does installation type change the math?
The recovered script does not read the installation type field; it uses fixed 75°C copper/aluminum ampacity maps. NM-B or other methods may require additional limits (for example NEC 334.80) beyond this page.

Related calculators