BuyNEC 314.16 — cubic inches, conductor equivalents, pass/fail vs box volume
Overfilled boxes violate code and risk damaged insulation. This tool totals conductor equivalents from your counts and compares required volume to the stamped box size.
Overfilled electrical boxes are a code violation and a real safety hazard. Cramming too many wires and devices into a box damages insulation and makes future work dangerous. NEC 314.16 specifies how many cubic inches each element requires. This calculator adds it up and tells you whether your box is legal — and if not, how much you are over.
| Item | 14 AWG | 12 AWG | 10 AWG | 8 AWG | 6 AWG | Counting rule |
|---|---|---|---|---|---|---|
| Each insulated conductor | 2.00 | 2.25 | 2.50 | 3.00 | 5.00 | 1 unit per conductor |
| All grounds combined | 2.00 | 2.25 | 2.50 | 3.00 | 5.00 | 1 unit total (largest EGC) |
| Internal cable clamps | 2.00 | 2.25 | 2.50 | 3.00 | 5.00 | 1 unit total regardless of count |
| Each single-gang device/yoke | 4.00 | 4.50 | 5.00 | 6.00 | 10.00 | 2 units per yoke |
| Luminaire stud or hickey | 2.00 | 2.25 | 2.50 | 3.00 | 5.00 | 1 unit each |
| Pigtails in box | 0 | 0 | 0 | 0 | 0 | Not counted if both ends in box |
| Box type | Volume (cu in) | Typical use |
|---|---|---|
| Small single-gang plastic | 18.0 | Basic switch or outlet, minimal wiring |
| Standard single-gang plastic | 20.3 | Most residential outlets and switches |
| Deep single-gang plastic | 22.5 | GFCI, dimmer, or multiple conductors |
| Standard 2-gang plastic | 34.0 | Two devices side by side |
| Deep 2-gang plastic | 42.0 | Two devices with heavy wiring |
| 2x4 shallow metal | 12.5 | Very limited — avoid if possible |
| 2x4 standard metal | 18.0 | Basic metalwork applications |
| 2x4 deep metal | 21.0 | More room for metalwork |
| 4" square 1-1/4" deep | 29.5 | Junction boxes, panel feeders |
| 4" square 1-1/2" deep | 42.0 | Larger junction boxes |
| 4" square 2-1/8" deep | 57.2 | Heavy wiring, multiple circuits |
| 4" octagon 1-1/2" deep | 15.5 | Ceiling fixtures, light loads |
| 4" octagon 2-1/8" deep | 21.5 | Ceiling fixtures, more wiring |
Per NEC 314.16. Always verify with current NEC and local code requirements. More tools at TestTalkHQ.com

One page. Voltage drop lengths, breaker and wire pairing, motor FLC.
$3.99
Buy
15 pages. Ampacity, corrections, voltage drop, motor circuits, conduit fill.
$12.99
Buy
Quote electrical work and flag panel headroom before you price it.
Excel or Google Sheets. Best on a computer.
$29.00
Buy
Card, 15-page guide and the estimator workbook. All six files.
Excel or Google Sheets. Best on a computer.
$34.99
$45.98 if bought separately — save $10.99
BuyCheckout opens in a new tab.
Deep old-work boxes, TR receptacles, strippers, wire for homeruns, and breaker finders for safe remodel work.
As an Amazon Associate, TestTalkHQ earns from qualifying purchases.
Box fill is one of those code calculations that catches people off guard on remodels. This calculator follows NEC 314.16(B). Use it like this:
Packed boxes risk insulation damage and heat buildup. NEC 314.16 sets minimum cubic inches per conductor equivalent. For how conduit space differs from box space, see Conduit fill explained the right way.
Each category gets conductor equivalents; each unit uses the volume for the largest wire size present (14 AWG = 2.00 cu in per unit through 6 AWG = 5.00 cu in per unit in this calculator’s table).
Use the allowance for the largest conductor for every unit in the same box — no averaging.
One 12-2 with ground, one duplex in 20.3 cu in: 2 conductors + 1 ground + 1 device (2 units) = 5 units × 2.25 = 11.25 cu in — passes with margin.
Four conductors + 1 ground + 1 device = 7 units × 2.25 = 15.75 cu in — still usually fine in 20.3 cu in. A third cable pushes you toward the limit.
Five 12-2 cables, splice only, 29.5 cu in: 10 + 1 ground = 11 units × 2.25 = 24.75 cu in — passes until you add clamps, devices, or more cables.