View on Amazon →NEC 430.24 feeder conductors: sum of all motor table FLAs + 25% of the highest-rated motor FLA. NEC 430.53(C) group branch OCPD: Table 430.52 allowance for the largest motor plus the FLA of every other motor on the circuit — device rating must not exceed that ceiling. Each motor still needs its own overload (430.32).
Full walkthrough: Grouped Motor Circuit Sizing Guide. Single-motor chart: Motor Circuit Sizing Chart.