NEC Wire Ampacity Tables — THHN, THWN, Copper & Aluminum Reference

⚡ NEC Wire Ampacity Tables

NEC Table 310.16 — allowable ampacities for insulated conductors rated up to 2000V in raceway, cable, or earth. Copper and aluminum. Includes temperature correction and conduit fill derating factors.




Copper — THHN / THWN-2 (90°C)

NEC Table 310.16 — 75°C column used for terminations per NEC 110.14(C)

Copper

AWG / kcmil Area (in²) 60°C Amps 75°C Amps 90°C Amps Common Use
#14 AWG 0.0097 15 20 25 Lighting, general circuits
#12 AWG 0.0133 20 25 30 20A circuits, receptacles
#10 AWG 0.0211 30 35 40 30A circuits, dryers, EV
#8 AWG 0.0366 40 50 55 40-50A circuits, ranges
#6 AWG 0.0507 55 65 75 60A sub-panels, AC
#4 AWG 0.0824 70 85 95 100A feeders
#3 AWG 0.0973 85 100 110 100A service
#2 AWG 0.1158 95 115 130 100-125A service
#1 AWG 0.1562 110 130 150 150A feeders
#1/0 AWG 0.1855 125 150 170 150-200A service
#2/0 AWG 0.2223 145 175 195 200A service
#3/0 AWG 0.2679 165 200 225 200A service entrance
#4/0 AWG 0.3237 195 230 260 200-400A service
250 kcmil 0.3970 215 255 290 Large feeders
300 kcmil 0.4608 240 285 320 Large feeders
350 kcmil 0.5242 260 310 350 400A service
400 kcmil 0.5917 280 335 380 Large commercial
500 kcmil 0.7073 320 380 430 Large commercial service
75°C column is the one you use
Even though THHN is rated 90°C, NEC 110.14(C) limits you to the 75°C column when terminations (breakers, lugs, connectors) are rated 75°C — which is almost always the case. Use the 75°C column for sizing. Use 90°C only for derating calculations.
Source: NEC Table 310.16 — Allowable Ampacities of Insulated Conductors Rated Up to and Including 2000 Volts. Ambient temperature 30°C (86°F). Not more than 3 current-carrying conductors in raceway.

Aluminum — XHHW-2 / THWN-2 (90°C)

NEC Table 310.16 — aluminum and copper-clad aluminum conductors

Aluminum

AWG / kcmil Area (in²) 60°C Amps 75°C Amps 90°C Amps Copper Equiv.
#12 AWG 0.0133 15 20 25 #10 Cu
#10 AWG 0.0211 25 30 35 #8 Cu
#8 AWG 0.0366 30 40 45 #6 Cu
#6 AWG 0.0507 40 50 60 #4 Cu
#4 AWG 0.0824 55 65 75 #3 Cu
#3 AWG 0.0973 65 75 85 #2 Cu
#2 AWG 0.1158 75 90 100 #1 Cu
#1 AWG 0.1562 85 100 115 #1/0 Cu
#1/0 AWG 0.1855 100 120 135 #2/0 Cu
#2/0 AWG 0.2223 115 135 150 #3/0 Cu
#3/0 AWG 0.2679 130 155 175 #4/0 Cu
#4/0 AWG 0.3237 150 180 205 250 kcmil Cu
250 kcmil 0.3970 170 205 230 300 kcmil Cu
300 kcmil 0.4608 190 230 255 350 kcmil Cu
350 kcmil 0.5242 210 250 280 400 kcmil Cu
400 kcmil 0.5917 225 270 305 500 kcmil Cu
500 kcmil 0.7073 260 310 350
Aluminum wire — use anti-oxidant compound
Aluminum conductors require anti-oxidant compound at all terminations to prevent oxidation and maintain connection integrity. Never use aluminum for branch circuits — feeders and service entrance only. Always use terminals rated for aluminum (marked AL or AL/CU).
Source: NEC Table 310.16. Aluminum and copper-clad aluminum conductors. Ambient temperature 30°C (86°F). Not more than 3 current-carrying conductors in raceway.

Derating Factors

NEC Table 310.15(B) temperature correction and Table 310.15(C)(1) conduit fill

Reference

Conduit Fill — More than 3 Current-Carrying Conductors
4–6 conductors × 0.80 (80%)
7–9 conductors × 0.70 (70%)
10–20 conductors × 0.50 (50%)
21–30 conductors × 0.45 (45%)
31–40 conductors × 0.40 (40%)
41+ conductors × 0.35 (35%)
Temperature Correction — 90°C Conductors (THHN)
21–25°C (70–77°F) × 1.04
26–30°C (79–86°F) × 1.00 (baseline)
31–35°C (88–95°F) × 0.96
36–40°C (97–104°F) × 0.91
41–45°C (106–113°F) × 0.87
46–50°C (115–122°F) × 0.82
51–55°C (124–131°F) × 0.76
56–60°C (133–140°F) × 0.71
61–70°C (142–158°F) × 0.58
71–80°C (160–176°F) × 0.41
Temperature Correction — 75°C Conductors (THWN)
21–25°C (70–77°F) × 1.05
26–30°C (79–86°F) × 1.00 (baseline)
31–35°C (88–95°F) × 0.94
36–40°C (97–104°F) × 0.88
41–45°C (106–113°F) × 0.82
46–50°C (115–122°F) × 0.75
51–55°C (124–131°F) × 0.67
56–60°C (133–140°F) × 0.58
How to Apply Both Derating Factors
Step 1 Find base ampacity from Table 310.16 (90°C column)
Step 2 Multiply by temperature correction factor
Step 3 Multiply by conduit fill factor
Step 4 Result must exceed your load current
Step 5 Final ampacity cannot exceed 75°C column value

Equipment grounding conductors don’t count
Equipment grounding conductors (EGC) do not count as current-carrying conductors for the purpose of conduit fill derating. Neutrals count only if they carry harmonic currents (e.g. in circuits with nonlinear loads like VFDs). For standard circuits, the neutral does not count.

Quick Breaker Size Reference

Minimum wire gauge for common breaker sizes — copper THHN at 75°C

Quick Ref

Breaker Size Min Copper Wire Min Aluminum Wire Voltage Drop Note
15A #14 AWG N/A (no Al branch) Under 50ft — fine. Over 100ft — go to #12
20A #12 AWG N/A (no Al branch) Under 75ft — fine. Over 150ft — go to #10
30A #10 AWG #8 AWG Al Under 100ft — fine. Long runs size up
40A #8 AWG #6 AWG Al Check voltage drop on runs over 75ft
50A #8 AWG #6 AWG Al Check voltage drop on runs over 75ft
60A #6 AWG #4 AWG Al Always check voltage drop
100A #4 AWG #2 AWG Al Always run voltage drop calc
125A #2 AWG #1/0 AWG Al Always run voltage drop calc
150A #1 AWG #2/0 AWG Al Always run voltage drop calc
200A #3/0 AWG #4/0 AWG Al Always run voltage drop calc
400A 350 kcmil 500 kcmil Al Large commercial — always engineer
Minimum wire sizes based on NEC Table 310.16 at 75°C column. Voltage drop not included — run a separate calculation for runs over 50 feet.

How to Read These Tables

The ampacity values in NEC Table 310.16 assume three conditions: ambient temperature of 30°C (86°F), no more than 3 current-carrying conductors in a raceway, and the conductor type shown. If any of those conditions differ on your job, you must derate.

  • Which column to use — use the 75°C column for almost all termination work. NEC 110.14(C) limits you to 60°C or 75°C at terminations depending on the equipment rating. Modern breakers and panels are typically rated 75°C, so the 75°C column applies. Use the 90°C column only when calculating derated ampacity starting point.
  • More than 3 conductors in conduit — apply the conduit fill derating factor from NEC Table 310.15(C)(1). Multiply your base 90°C ampacity by the factor, then confirm the result doesn’t exceed the 75°C column value.
  • High ambient temperature — apply the temperature correction factor. Attics, boiler rooms, rooftop conduit in summer — these environments push ambient temperature well above 30°C and require derating.
  • Both derating factors apply — when you have both more than 3 conductors AND high ambient temperature, apply both factors. Multiply the 90°C base ampacity by both correction factors. The result is your corrected ampacity.

Copper vs Aluminum — When to Use Each

Aluminum wire is significantly cheaper than copper for the same ampacity but requires one to two gauge sizes larger. For service entrances and large feeder runs, aluminum is standard practice and cost-effective. For branch circuits, copper is required — aluminum branch wiring in homes has a documented history of connection failures and is not used in modern construction.

  • Use copper for — branch circuits (15A, 20A, 30A), motor circuits, any circuit where connection integrity is critical, short runs where the cost difference is minimal
  • Use aluminum for — service entrance conductors, large feeder runs (100A+), sub-panel feeds, anywhere copper cost is significant and proper termination is ensured
  • Aluminum termination rules — use anti-oxidant compound, terminals rated AL or AL/CU, proper torque per manufacturer spec. Never use aluminum with terminals rated CU only.

VoltKit — Electrical Calculators for the Job

Wire ampacity derating, voltage drop, conduit fill, load calculation, and more. Free on Android. Works offline on the job site.

Get VoltKit Free

When a table value or calculated derating still disagrees with an inspector or the field, use Wire Ampacity Troubleshooting. Re-run the adjustment chain with the Wire Ampacity & Derating Calculator.